Numéro gratuit : 800.554.1036

Produits

PF FE75 / FE100 Gas Pressure Regulator

The FE75 / FE100 is a two-stage, spring loaded direct acting gas pressure regulator by Pietro Fiorentini. It is particularly suitable for low pressure natural gas distribution systems for residential and commercial users. It should be used with previously filtered noncorrosive gases including biomethane and natural gas blended with hydrogen.

According to the International Standard ISO 23555-2 and European Standard EN 334, it is classified as Fail Close because it is always supplied with an over pressure protection device (slam shut valve). The FE75 / FE100 is Hydrogen Ready for NG-H2 blending.

Caractéristiques principales:
• Design pressure*: (PS1 / DP²) up to 860 kPa, up to 125 psig
• Ambient temperature*: (TS¹)**
Standard version: -30°C to +65°C | -20°F to +150°F
Arctic version: -40°C to +65°C | -40°F to +150°F
• Inlet gas temperature*,***:
Standard version: -20°C to +65°C | -4°F to +150°F
Arctic version: -30°C to +65°C | -20°F to +150°F
• Inlet pressure (MAOP / pumax¹): from 50 kPa to 0.86 MPa,from 7.25 psig to 125 psig
• Range of downstream pressureWds:
BP version:Wds: from 1.3 kPa to 16 kPa , from 5.2”w.c. to 2.3 psig
MP version: from 14 kPa to 35 kPa, from 2 psig to 5.1 psig
• Range of downstream pressure Wdso
BP version:Wds:from 3.2 kPa to 23.1 kPa, from 12.6” w.c. to 3.35 psig
MP version:from 21 kPa to 55.2 kPa, from 3 psig to 8 psig
• Range of downstream pressure Wdsu
BP version:Wds: from 0.6 kPa to 25 kPa, from 2.4” w.c. to 3.6 psig
• Minimum inlet pressure and nominal capacity:
FE75: up to 75 Sm³/h | 2,600 scfh with 50 kPa | 7.25 psig differential pressure
FE100: up to 100 Sm³/h | 3,500 scfh with 69 kPa | 10 psig differential pressure
• Lock up pressure class: 20, minimum 0.75 kPa | 3” w.c.
• Accuracy class (AC¹): 10
• Connections*: In-line 1”, 1”1/2 NPT according to ANSI B1.20.1, other configurations or connections on request

(¹) according to EN334 standard
(²) according to ISO 23555-1 standard
(*) NOTE: Different functional features and/or extended temperature ranges may be available on request. Stated inlet gas temperature range is the maximum for which the equipment’s full performance, including accuracy is guaranteed. Product may have a different pressure or temperature ranges according to the version and/or installed accessories.
(**) NOTE: Stated temperature range is the operating range for which the equipment’s mechanical resistance and leakage rate are guaranteed. Some body materials, if multiple choices are available, may not be suitable for all the available versions shown.
(***) NOTE: Stated temperature range is the range for which the equipment’s full performance, including accuracy and lock-up are guaranteed. Some body materials, if multiple choices are available, may not be suitable for all the available versions shown.

Competitive Advantages:
• Operates with low differential pressure
• Slam shut for overpressure – Slam shut for underpressure
• Two-stage double diaphragm and single orifice regulator
• Highly customizable
• Suitable for 1 ft clearance installation with 2.5 cf/h limited venting
• Built-in thermal valve option
• Built-in strainer
• Suitable for outdoor installations
• Biomethane (RNG) compatible and 20% Hydrogen blending compatible. Higher blending available on request

Téléchargements :
PF FE75/FE50 Technical Brochure
PF FE75/FE100 Product Flyer

Faire défiler vers le haut