Numéro gratuit : 800.554.1036

Produits

PF NeoR Double Stage Gas Regulator

The PF NeoR is a double stage gas pressure regulator by Pietro Fiorentini.
Designed to ensure continuous gas supply while maintaining a high level of safety with reduced emission.

The NeoR is a service regulator without slam-shut device, incorporating a double token relief valve (IRV) with partial relief capacity. It is particularly suitable for low pressure natural gas distribution systems for residential users. It should be used with previously filtered non-corrosive gases including biomethane and RNG (Renewable Natural Gas).

Le site NeoR is Hydrogen Ready for NG-H2 blending.

Sûr, fiable et haute performance

Traits:

  • Accuracy and lock-up pressure according to ANSI B109.4 and CSA 6.18
  • Connections: In-line / 90° configuration with 3/4” or 1” NPT according to ANSI B1.20.1, other configurations or connections on request
  • Inlet pressure: from 10 psig to 100 psig | from 69 kPa to 0.69 MPa
  • Ambient temperature: standard version from -20°F to +150°F | -30°C to +65°C, arctic version from -40°F to +150°F | -40°C to +65°
  • Range of downstream pressure Wds: from 5” w.c. to 2 psig | from 1.3 kPa to 13.8 kPa

NeoR Competitive Advantages:

  • Operates with low differential
  • Two-stage single orifice regulator
  • Overpressure protection without slam-shut or full capacity IRV
    Built-in thermal valve option
  • Suitable for outdoor installations
  • Built-in strainer
  • Biomethane (RNG) compatible and 3 ft or more clearance installation 20% Hydrogen blending compatible. Higher blending available on request
  • 3 ft or more clearance installation according to 49 CFR § 192